Customization: | Available |
---|---|
Warranty: | 10years |
Nature of Source Flow: | Passive inverter |
Still deciding? Get samples of US$ 2089/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Datasheet
|
MAC 30KTL3-X LV
|
MAC 40KTL3-X LV
|
MAC 50KTL3-X LV
|
MAC 60KTL3-X LV
|
Inputu data (DC)
|
||||
Max. recommended PV
power(for module STC)
|
45000W
|
60000W
|
75000W
|
90000W
|
Max.DC voltage
|
1100V
|
|||
Start voltage
|
250V
|
|||
Nominal voltage
|
600V
|
|||
MPPT voltage range
|
200V-1000V
|
|||
No. of MPP trackers
|
3
|
|||
No. of PV strings per MPP tracker
|
3/3/2
|
3/3/3
|
4/3/3
|
4/4/4
|
Max. input current per MPP tracker
|
37.5A/37.5A/25A
|
37.5A/37.5A/37.5A
|
50A/37.5A/37.5A
|
50A/50A/50A
|
Max. short-circuit current
per MPP tracker
|
45A
|
45A
|
55A
|
55A
|
Output data (AC)
|
||||
Rated AC output power
|
30000W
|
40000W
|
50000W
|
60000W
|
Max. AC apparent power
|
33300VA
|
44400VA
|
55500VA
|
66600VA
|
Nominal AC voltage(range*)
|
230V/400V (340-440V)
|
|||
AC grid frequency(range*)
|
50/60 Hz (45-55Hz/55-65 Hz)
|
|||
Max. output current
|
48.3A
|
64.4A
|
80.5A
|
96.6A
|
Adjustable power factor
|
0.8leading ...0.8lagging
|
|||
THDi
|
<3%
|
|||
AC grid connection type
|
3W+N+PE
|
|||
Efficiency
|
||||
Max. efficiency
|
98.7%
|
98.7%
|
98.7%
|
98.8%
|
European efficiency
|
98.4%
|
98.5%
|
98.5%
|
98.5%
|
MPPT efficiency
|
99.9%
|
|||
Protection devices
|
||||
DC reverse polarity protection
|
Yes
|
|||
DC switch
|
Yes
|
|||
AC/DC surge protection
|
Type II / Type II
|
|||
Insulation resistance monitoring
|
Yes
|
|||
AC short-circuit protection
|
Yes
|
|||
Ground fault monitoring
|
Yes
|
|||
Grid monitoring
|
Yes
|
|||
Anti-islanding protection
|
Yes
|
|||
Residual-current monitoring unit
|
Yes
|